Generator connection box, type 2, with MC4 connector for 2 x 1 string

Item no. 5088556 | EAN 4012196816088

5088556 / PVG-C1000S110
IP66
Product description

Product description

System solution, type 2, with MC4 connector for photovoltaic inverter with 2 separate MPP trackers

• Varistor arrester, connectable with cut-off unit in error-resistant Y circuit to VDE 0100-712 (50539-12)
• Low DC voltage protection level: < 4.0 kV (Voc max = 1,000V DC with V20-C/0-500PV)
• One PV string input (MC4 plug connector) at one MPP inverter input, up to 30A DC per terminal
• Pre-mounted in polycarbonate housing (IP66), UV-resistant for use outside

For DC protection of the inverter of photovoltaic systems.

If there is a danger of condensation forming through wind, ice, temperature or sunlight, further measures may be necessary!
  • 5-year warranty
  • Communautés Européennes, EC declaration of conformity according to EC directives
  • Protection device to DIN EN 61643-11 or IEC 61643-11
  • Transition from LPZ 1 to LPZ 2
  • Installation electrotechnical expertise
Technical data

Technical data

Anzahl MPPT 2
Ausgänge pro MPPT 1
Cable type for surge protection devices Power cable DC (PV)
Colour Light grey; RAL 7035
Conductor cross-section, flexible (fine-wire), min. 25 mm²
Conductor cross-section, rigid (single-wire/multiwire), max. 35 mm²
DC network form yes
Depth 113 mm
Dimension 1000V DC
Eingänge pro MPPT 1
Equipped with load-break switch no
Housing material PC
Installation type Pre-mounted in the housing
IT network form no
Lightning protection zone LPZ 1→2
Max. Input current per string 30 A
Max. Input voltage DC 1000 V
Max. Output current 30 A
Max. PV voltage 1000 V
Maximum back-up fuse 125 A
Maximum continuous voltage DC 1000
Maximum discharge current (8/20 μs) 40 kA
Monitoring function no
Network form DC
Nominal discharge current (8/20 µs) 20 kA
Number of cable entries 4
Number of inputs 1
Number of string inputs 1
Operating temperature, max. 80 °C
Operating temperature, min. -40 °C
Other network form no
Permitted temperature range, max. 60 °C
Permitted temperature range, min. -5 °C
Pole number 3
Protection rating IP66
Protection rating IK code IK05.
Remote signalling no
Response time <25 ns
Signalling on device Visual
SPD to EN 61643-11 Type 2
SPD to IEC 61643-1 Class II
Test class, type 1 no
Test class, type 2 yes
Test class, type 3 no
TN network form no
TN-C network form no
TN-C-S network form no
TN-S network form no
TT network form no
Type of entry MC4
Version for For two MPP trackers and with MC4 connection

Dimensions

Height 190 mm
Width 240 mm

Connectivity options

Anschlussart Generatoranschlusskasten MC4
Max. mains-side overcurrent protection 125
All types

All types

Types Protection rating Item no. Quantity SSU
PVG-C1000S110 IP66 5088556
1 piece
Accessories

System accessories

Products Types Item no. Quantity SSU
Weather protection roof for Ion charging station Basic/Key Weather protection roof for Ion charging station Basic/Key WB WPR 6570105
1 piece
Downloads

Download

Download

Download
Download

PVG-C1000S110 / 5088556
Download