Coaxial protection device for SMA connection: female/female

Item no. 5093277 | EAN 4012195867050

  • 5-year warranty
  • Transition from LPZ 0 to LPZ 2
  • Communautés Européennes, EC declaration of conformity according to EC directives
  • TV applications
  • SAT-TV applications
  • Installation electrotechnical expertise

Coaxial data cable protection devices • High pulse current carrying capacity 2 x 2.5 kA (10/350) • Simple mounting (adapter connector), m = connector, f = socket • Optimised transmission behaviour • 5-year guarantee • With SMA connector • Including OBO Multi-Quick clip 25-28 for simple installation • 50 Ω technology Application: Radio and data technology with SMA connector

All types

All types

Types Highest
continuous
voltage
AC
Maximum
continuous
voltage
DC
Number
of poles
Connec-
tion
system
Item no. Quantity SSU
DS-SMA W/W 130 V 185 V 1 SMA 5093277
1 piece
Coaxial protection device for SMA connection: female/female
Coaxial protection device for SMA connection: female/female

Coaxial protection device for SMA connection: female/female

Item no. 5093277

Data sheet, 0.13MB, pdf
Download

Technical data

Arrestor monitoring no
Category Type 1+2 / D1+C2
SPD to IEC 61643-21 Class I+II / D1+C2
Number of poles 1
Insertion loss ≤0,2 dB
Explosion-tested version no
Telecommunications contact no
Total discharge current (8/20) 10 kA
Total discharge current (10/350) 5 kA
Frequency range 0 - 3,7 GHz
Frequency range 0 - 3700 MHz
Cut-off frequency 3700 MHz
Maximum continuous voltage AC 130 V
Maximum continuous voltage DC 185 V
Insulation resistance >1 GΩ
Impulse discharge current (10/350) 2.5 kA
Capacity (wire-wire) <10 pF
Capacity (wire-earth) <10 pF
Lightning protection zone LPZ 0→2
Rated current 10 A
Nominal load current AC 7 A
Nominal load current DC 10 A
Installation type Connector/cable adapter
Testing standard IEC 61643-21
Return loss ≥14 dB
Shielding connection available Yes
Shield connection Direct
Protection rating IP40
Protection level <800 V
Protection level wire-wire <800 V
Protection level wire-earth <800 V
Signalling on device None
Connection system SMA
Impulse durability wire-wire C2: 10 kV / 5 kA (8/20µs)
Impulse durability wire-earth C2: 10 kV / 5 kA (8/20µs)
Temperature range -40 - +80 °C
Wave resistance 50 Ω
Invitation to tender text

Invitation to tender text

DS-SMA W/W / 5093277
Download
Downloads

Data sheet

DS-SMA W/W / 5093277, 0.13MB, pdf
Download

Instructions and Aid

Surge protection made easy – TBS selection aid, 0.88MB, pdf
Download
Surge protection selection aid, 2.65MB, pdf
Download
Lightning protection guide, 25.41MB, pdf
Download